How to balance radiators using the lockshield valves

Balance radiators by closing the lockshields on the fastest-heating ones until each gets the right flow-to-return temperature drop. Steps, targets, pitfalls.

The short answer

To balance radiators, open every valve fully, note the order the radiators heat up, then partly close the lockshield valve on the fastest ones so flow is pushed to the slow ones. With clip-on thermometers, aim for the flow and return pipe temperature drop your boiler maker specifies, typically around 20°C for a condensing gas boiler.

Key points

  • Balancing is done on the lockshield valve, the capped one, not the thermostatic valve you turn by hand.
  • Radiators nearest the boiler or pump heat first and need restricting the most. The furthest radiator is usually left fully open.
  • Some popular guides quote a 12°C drop. The heating industry council's consumer guide gives around 20°C for condensing gas boilers, and says to check the boiler maker's figure.
  • Bleed the system and rule out sludge first, because balancing cannot fix a blocked radiator.
  • Heat pumps and low flow temperatures make balancing matter more, because there is less spare heat to cover a starved radiator.

If the radiators near your boiler are too hot to touch while the back bedroom never warms up, the system is probably out of balance. Hot water takes the easiest route, so radiators on short pipe runs grab most of the flow and the distant ones get what is left. Balancing fixes that by slightly restricting the greedy radiators. It needs a spanner, some patience and ideally a pair of clip-on thermometers. This post covers the method engineers use, the temperature target, how heat pumps change things, and what to do when balancing does not work.

Why some radiators are hot and others stay cold

The HHIC consumer guide to balancing (opens in a new tab)1 explains it simply. Each radiator needs a certain flow of water to give its proper heat output. If the flow is not balanced, some radiators take the bulk of the hot water from the boiler and others are left with little, so some rooms are too hot and others stay cold.

The same guide names a common cause: radiators taken off for decorating and then refitted, which can upset the balance of the whole system. It also warns against the usual workaround of turning the pump speed or boiler temperature up to push heat to the cold rooms. That may or may not help the cold radiators, but it raises the energy the system uses and can make radiator valves noisy.

Before you start adjusting valves, make sure it really is a balance problem. A radiator that is cold at the top needs bleeding, and one that is cold at the bottom has sludge in it. Balancing fixes neither, so if you see either pattern, start with our guide to a radiator cold at the bottom instead.

Lockshield valve or TRV: which one do you adjust?

Most radiators have a valve at each bottom corner, and only one of them is used for balancing. Systems are normally balanced by adjusting the lockshield valves, usually fitted on the return side of each radiator.

The two radiator valves and their jobs
ValveHow to recognise itWhat it doesUse it for balancing?
Thermostatic valve (TRV)Numbered head, usually 0 or star to 5Opens and closes to hold the room temperatureNo, set it fully open while balancing
Manual wheel-head valvePlain cap you turn by handTurns the radiator on or offNo, set it fully open
Lockshield valvePlain plastic cap that just spins or pulls offSets how much water the radiator can takeYes, this is the balancing valve

Finding the flow and return

The flow pipe is the one that gets hot first when the heating starts. The return is the other one. Lockshields are usually on the return, but on some radiators the pipework runs the other way, so feel both pipes a minute after the heating comes on rather than assuming.

Before you start balancing

Balancing a system with air or sludge in it gives misleading results, so get the basics right first. Pick a cool day with the house cold, because you will be turning the heating off and on.

Be realistic about the job. Vaillant's guidance on hydraulic balancing (opens in a new tab)7 (on its international site) says it is a precise process best handled by professionals, and stresses bleeding the radiators first for accurate readings. The lockshield method here is a fair DIY job for a simple system, but if yours has zones, a heat pump or radiators that never respond, get it done properly.

  • Bleed every radiator and top the boiler back up if it is a combi. Our guide to bleeding radiators and repressurising covers this.
  • Check the boiler pressure is in the normal band on the gauge before you begin.
  • Turn every TRV to its highest setting and every manual valve fully open.
  • Pull the caps off all the lockshields and open each one fully anticlockwise, counting the turns so you know where it started.
  • Get a lockshield key or small adjustable spanner, a notepad, and ideally two clip-on pipe thermometers or an infrared thermometer.
  • Turn room thermostats up high, and put any smart TRVs or zone controls into manual, fully open mode, so the boiler keeps firing and nothing switches off while you work.

How to balance radiators step by step

These steps follow the method in HHIC's consumer leaflet. Allow a couple of hours in a typical house, mostly waiting for radiators to settle.

  1. Let the system go coldWith all valves fully open, switch the heating off and wait until every radiator is cold.
  2. Record the heating orderTurn the heating on and go round the house writing down the order the radiators start to warm. Those nearest the pump normally get hot first. Where the pump is inside the boiler, the radiator nearest the boiler usually heats first.
  3. Check whether you need to adjust at allIf every radiator heats up at about the same rate with all valves open, the system is already balanced and you can stop here.
  4. Restrict the fastest radiatorGo to the first radiator on your list and close its lockshield clockwise. HHIC suggests starting by restricting the hottest radiators by 50 to 60%, roughly half. In practice most of the effect happens in the last half turn before closed, so close the lockshield, open it a little at a time, and let the thermometers tell you when you are there.
  5. Measure and fine-tuneClip one thermometer on the flow pipe and one on the return. Adjust the lockshield until you get the temperature drop your boiler maker recommends, allowing a couple of minutes after each tweak for the reading to settle.
  6. Work down the listRepeat on each radiator in the order they heated up. Each one will usually need less restriction than the one before. The last, slowest radiator is normally left fully or nearly fully open.
  7. Go round againChanging one radiator affects all the others, so recheck the early ones once you reach the end. A poorly designed system may need some valves closed more than 80%.
  8. Refit the caps and reset the TRVsPut the lockshield caps back on, write the turns for each radiator on your notepad, and set the TRVs back to the room temperatures you want.

Trade tip

Write the turns down

Keep a note of how many turns open each lockshield is set to, room by room. When a radiator comes off for decorating, you can close the lockshield, count the turns, and put it back exactly. That one habit saves rebalancing the whole house every time a room is painted.

What temperature difference should you aim for?

This is where the advice online disagrees. Ageas's balancing guide (opens in a new tab)5, for example, tells you to adjust until there is a 12°C difference between the two pipes. HHIC's leaflet says the drop is typically 20°C for condensing gas boilers, and to always check the appliance manufacturer's guidance. The difference matters, because a condensing boiler only condenses, and so only reaches its best efficiency, when the water coming back to it is cool enough.

An article on The Heating Hub (opens in a new tab)2, written by a product manager at the controls maker Drayton, makes the same point: correct balancing means a return temperature around 20°C below the flow, and condensing boilers lose efficiency when they run too hot. If you balance to a 12°C drop on a modern condensing boiler, the house may feel warm, but the return water is likely to be too hot for the boiler to condense as well as it could.

Without thermometers you can still balance by touch, aiming for every radiator to heat at roughly the same rate with the returns noticeably cooler than the flows. It is less precise, but it fixes the usual cold-bedroom complaint.

Here is how the readings typically look in practice, as an illustration of trade practice rather than a specific house. On an unbalanced system, the radiator next to the boiler often shows its return pipe almost as hot as its flow, because water is rushing straight through it, while the radiator in the far bedroom has a lukewarm flow pipe. As you close the first lockshield, its return drops and the far radiator's flow pipe warms up. That shift is the sign you are moving water in the right direction.

Balancing for a heat pump or a lower flow temperature

Building regulations now push wet heating systems towards lower temperatures. Approved Document L, Volume 1 (opens in a new tab)3 says that where a wet heating system is newly installed or fully replaced, the pipework and emitters should be sized so the system can meet the home's heating needs at a maximum flow temperature of 55°C or lower. That guidance applies in England; Wales has its own Approved Documents. The 2026 edition (opens in a new tab)6, which takes effect on 24 March 2027, keeps the 55°C limit in paragraph 4.10.

At those temperatures there is far less spare heat in each radiator, so a radiator that is short of flow simply cannot warm its room. That is why balancing is treated as part of the design on a heat pump system rather than an afterthought. The target drop on a heat pump system comes from the installer's design for that house. The 20°C figure is HHIC's guide for condensing gas boilers, so do not apply it to a heat pump.

If you are thinking about a heat pump, getting the radiators sized and balanced is a big part of whether it performs. Our air source heat pump installs start with that check, our guide to heat pumps in older homes covers period properties, and our post asking whether heat pumps are worth it looks at running costs honestly.

When balancing doesn't fix the cold rooms

If you have balanced carefully and a room is still cold, the problem is somewhere else. These are the usual culprits.

Problems that balancing will not cure
What you noticeLikely causeNext step
One radiator cold even fully openSludge, an air lock or a blocked valveFlush the radiator or have the valve checked
Radiator hot but room still coldRadiator too small for the room's heat lossHave the heat loss and radiator size checked
TRVs whistle or hiss as they closeToo much flow through those valvesRestrict the lockshields further
Everything lukewarm, boiler runningPump, valve or boiler settingBook an engineer
Balance drifts every few weeksSmart TRVs or zone valves changing the flowAsk about automatic balancing valves

Automatic and pre-settable valves

The HHIC guide notes that some modern TRVs can be balanced using internal settings on the valve body, chosen from a lookup table for the room and radiator size. The Heating Hub also points out that as TRVs open and close through the day, the pressure at each open valve changes, and describes auto-balancing TRVs that adjust for this. They are worth considering if you are replacing valves anyway, particularly with smart heating controls.

When to call a professional

When to get an engineer in

If the radiators still heat unevenly after a careful balance, or the boiler struggles, book a boiler service and system check. The engineer can look at the pump, the boiler's flow temperature and the system water. Anything inside the boiler casing must be done by an engineer on the Gas Safe Register, and the HSE strongly encourages checking the engineer's ID card (opens in a new tab)4 before work starts. If you smell gas, call 0800 111 999.

If you would rather have it done properly with thermometers, or the cold rooms are still cold after balancing, call 07858 305739 or ask us to take a look.

Sources and further reading

  1. Consumer Guide: Balancing the central heating system (opens in a new tab), Heating and Hotwater Industry Council (HHIC). Why systems go out of balance, lockshields on the return, heating order, 50 to 60% and 80% restriction, typical 20°C drop for condensing boilers, TRV noise, pre-settable TRVs, lower boiler temperature after balancing
  2. The untapped efficiency benefits of radiator balancing (opens in a new tab), The Heating Hub (article by David Kempster, Product Manager, Schneider Electric/Drayton). Return around 20°C below flow; condensing efficiency; TRVs changing pressure through the day; auto-balancing TRVs
  3. Approved Document L: Conservation of fuel and power, Volume 1: Dwellings (2021 edition incorporating 2023 amendments) (opens in a new tab), GOV.UK. Paragraph 5.10: new or fully replaced wet heating systems sized to run at a maximum flow temperature of 55°C or lower
  4. Gas safety: frequently asked questions (domestic) (opens in a new tab), Health and Safety Executive. Gas work by a Gas Safe registered engineer; check the engineer's ID card; gas emergency number 0800 111 999
  5. How to balance your radiators (opens in a new tab), Ageas. Example of a popular guide advising a 12°C flow-to-return difference
  6. Approved Document L: Energy and greenhouse gas emissions, Volume 1: Dwellings (2026 edition) (opens in a new tab), GOV.UK. Takes effect in England on 24 March 2027; paragraph 4.10 keeps the 55°C maximum flow temperature for new or fully replaced systems
  7. Hydraulic balancing (opens in a new tab), Vaillant. Hydraulic balancing is best handled by professionals; bleed radiators before balancing

Sources checked on 4 November 2026.

About this guide

Written by the team at CLA Developments, who do plumbing, heating, building and tiling work across Gloucestershire and the Cotswolds, and reviewed by Alistair Hunt, who leads the team on site. Customers on Checkatrade (opens in a new tab) mention him by name for bathroom refits, tiling and plumbing repairs. The facts were checked against the sources listed above. This is general guidance, not a survey of your home. Gas work must be done by a Gas Safe registered engineer, new electrical circuits by a qualified electrician, and structural changes need a structural engineer and building control. Spotted something out of date? Email us and we will correct it.

FAQ

More questions

Can't see yours? Call or email and you'll speak to the people who do the work.

Yes. A TRV switches a radiator off when the room reaches its set temperature, but it does nothing about how much water the radiator takes while it is heating. A radiator near the boiler can still hog the flow until its TRV closes, leaving distant rooms waiting. The HHIC guide also notes that TRVs with too much flow can be noisy as they start to close.

It can. HHIC says that once a system is balanced, the boiler can in most cases run at a lower temperature, which improves efficiency. How much you save depends on how far out the system was to begin with, and we would not trust a single headline figure. The bigger win is often comfort, with every room warming at the same time.

Run the heating from cold and feel each radiator over the first twenty minutes. If the ones near the boiler are hot within a few minutes while distant rooms take much longer or never get fully warm, the system is out of balance. Upstairs rooms at the end of a long pipe run are the usual victims. If every radiator heats at a similar pace, leave the lockshields alone.

Usually, at least partly. A new radiator may be a different size or output from the old one, and its lockshield starts fully open, so it can pull flow away from the rest of the house. Set its lockshield to give the right temperature drop, then check the radiators either side of it on the system. Our radiator and heating installs include balancing as standard.

Not in quite the same way. Some older houses have a one-pipe system, where water flows through a single loop and each radiator takes a share as it passes. Radiators further round get cooler water whatever you do with the lockshields. If your radiators get steadily cooler around the house even with careful balancing, it is worth having the pipework identified before spending more time on valves.